top of page
GENERATOR TECHNICAL DATA
GENERATOR RENTAL RANGE 20kVA TO 2000kVA
Size kVA | Length (mm) | Length (mm) | Height (mm) | Weight Dry (kg) | Fuel Capacity (l) | 50% Load (l/hr) | 75% Load (l/hr) | 100% Load (l/hr) |
|---|---|---|---|---|---|---|---|---|
20kVA
| 1685
| 950
| 1485 | 730
| 45 | 2.9 | 3.9 | 5.30 |
30kVA | 2102 | 970 | 1525 | 1002 | 161 | 4 | 5.7 | 7.4 |
45kVA
| 2300 | 1120 | 1525 | 1293 | 219 | 5.8 | 7.5 | 9.2 |
65kVA | 2300
| 1120
| 1525
| 1319
| 219
| 7.8
| 12.3 | 16.3
|
PRO100kVA | 2770
| 1120 | 1847
| 2027 | 410 | 14.6 | 20.4 | 23.5 |
110kVA | 2770 | 1120 | 1525 | 1744 | 250 | 12.9 | 18.9 | 23.8 |
PRO150kVA | 3520 | 1120 | 2226 | 2547 | 590 | 16.4 | 24.7 | 33.4 |
150kVA | 3520 | 1120 | 1815 | 2158 | 349 | 19.9 | 28.1 | 33.5 |
200kVA | 3894 | 1300 | 1996 | 2944 | 550 + | 26.8 | 37.6 | 48.7 |
275kVA
| 4300 | 1300 | 2259 | 3800 | 757 + | 27.5 | 41.25 | 55
|
PRO300kVA | 4065
| 1400
| 2124 | 3880
| 592.6 | 33.8
| 47.3 | 62.5 |
400kVA
| 4930 | 1658 | 2317 | 4655 | 887
| 36.2
| 53
| 69.6
|
All weights and measurements are for indicative purposes only. The information contained above is for guidance only and is subject to change without notice or liability. All information is provided in good faith.
CABLE TECHNICAL DATA
H07RN-F RUBBER CABLE CURRENT CARRYING CAPACITIES
Cable Description (mm) | Current Capacity (Amps) | Overall Diameter (mm) | Cable Weight (kg/m) |
|---|---|---|---|
2.5mm 3 Core 1ph
| 29 | 11.48
| 0.21 |
6mm 3 Core 1ph
| 52
| 14.78
| 0.39
|
16mm 3 Core 1ph
| 86
| 23.31
| 1.031
|
35mm 3 Core 1ph
| 140
| 30.2 | 1.907
|
2.5mm 5 Core 3ph
| 29
| 14
| 0.32
|
6mm 5 Core 3ph
| 52
| 18.2
| 0.63
|
16mm 5 Core 3ph
| 86
| 28.2
| 1.53
|
35mm 5 Core 3ph
| 140
| 37.2
| 3.59
|
35mm Single Core
| 192
| 14.6
| 0.52
|
50mm Single Core
| 240
| 17.2
| 0.72
|
70mm Single Core
| 297
| 19.35
| 0.97
|
95mm Single Core
| 354
| 22.2
| 1.24
|
ph = Phase
The above technical data is for indicative purposes. The information contained above is for guidance only and is subject to change without notice or liability. All information is provided in good faith.
ELECTRICAL FORMULA
To Find | Single-Phase | Three-Phase |
|---|---|---|
Kilowatts | Amps x Volts x PF / 1000
| Amps x Volts x 1.732 x PF / 1000
|
kVA
| Amps x Volts / 1000
| Amps x Volts x 1.732 / 1000
|
Amperes KW known
| (KW x 1000) / (Volts x PF)
| (KW x 1000) / (1.732 x Volts x PF)
|
Amperes kVA known
| kVA x 1000 / Volts
| (kVA x 1000) / (1.732 x Volts)
|
bottom of page